Global Data (Publish/ Subscribe)
198
33002479 06 07/2008
Downloading a
glbdat.ini File to
another NOE
Verifying System
Operation
Step Action
1 At the DOS prompt type FTP followed by the IP address and press Enter.
2 At the User prompt type the FTP username and press Enter.
3 At the password prompt enter your FTP Password and press Enter.
4 At the FTP prompt type cd wwwroot/conf/glbdata and press Enter.
5 At the FTP prompt type put and press Enter.
6 At the local file prompt type glbdata.ini and press Enter.
7 At the remote file prompt type glbdata.ini and press Enter.
Step Action
1 Verify all controllers are running.
2 Look at the health of all variables using the Global Data Diagnostic page.
Follow these links: | Diagnostics | NOE Diagnostics | Global Data