Schneider Automation Modicon Quantum Ethernet Manuel d'utilisateur Page 181

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 382
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 180
Transferring Data Using Communication Blocks
33002479 06 07/2008 181
Write CTE
Description A write CTE operation writes the CTE configuration table from the specified data
(DATABUF) to a specified Ethernet configuration extension table or to a specific slot.
To program an MBP_MSTR block to perform a write CTE operation, use function
code 12 (see Operational Function Codes, p. 151).
Network
Implementation
A write CTE operation can be performed on TCP/IP Ethernet (see TCP/IP Ethernet
Network Statistics, p. 174) and SY/MAX Ethernet networks.
Control Block
Usage for TCP/IP
Ethernet
Register Meaning
CONTROL[1] 12 = write CTE
CONTROL[2] Indicates the error status
CONTROL[3] The length setting: a value from 12 to 37.
CONTROL[4] No significance
CONTROL[5] Routing register
Least significant byte = mapping index
Either a value displayed in the byte of the address or is not used.
or
Most significant byte = network adapter module slot
CONTROL[6]
...
CONTROL[9]
The number shown in the least significant byte in the area 1 through 16
indicates the slot where the optional module is located.
Vue de la page 180
1 2 ... 176 177 178 179 180 181 182 183 184 185 186 ... 381 382

Commentaires sur ces manuels

Pas de commentaire