Schneider Automation Modicon Quantum Ethernet Manuel d'utilisateur Page 250

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 382
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 249
Using the NTPTime Service
250
33002479 06 07/2008
Configuring the Quantum 140 NOE 771 11 NTP Time Service
Configuring the
NTP Time
Service
Configure or change the following parameters on the NTP Configuration page.
Model Family Module Address
Module Utilities
TCP/IP 10/100 Regular connection
Rack
Module Channel
No
No
Yes
No
Yes
IO Scanning
SNMP
Address Server
NTP
Global Data
Module IP Address
IP Address Subnetwork Mask Gateway Address
IP Configuration Messaging IO Scanning Global Data SNMP Address Server NTP Bandwidth
NTP Server Configuration
IP address of Primary NTP Server
IP address of Secondary NTP Server
Polling period seconds
Time Zone
(GMT)Greenwich Mean Time(Dublin Edinburgh Lisbon London)
Automatically adjust clock for daylight saving change
Ethernet_1
Field Parameter Action
NTP Server Configuration
IP address of primary NTP server Enter a valid IP address
IP address of secondary NTP server Enter a valid IP address
Polling Period (in seconds Enter a value
z min = 1sec
z max = 120sec
z default = 5 sec
Time Zone Select from the drop-down menu:
z Universal Time, Coordinated (GMT)
= default
z Custom time zone
Vue de la page 249