Maintenance
330
33002479 06 07/2008
Kernel LED Error The following table describes the Kernel LED errors that may occur and how to
respond to them.
Fault LED The Fault LED will flash briefly following an error as the module attempts to recover.
The following figure shows the Fault LED.
If Then
The Ready LED is on and the Kernel LED is
flashing
The module has detected an invalid software
image.
The Ready LED is on and the Kernel LED is
shining steadily,
An attempt to download a software image has
failed and the module is in kernel mode.
Either of the above conditions exists. Download a new NOE Exec (see
Downloading a New NOE Exec, p. 334).