Schneider Automation Modicon Quantum Ethernet Guide de l'utilisateur Page 279

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 900
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 278
Networking
35013379 02 October 2007 279
Rear Panel
Switches
Two rotary switches are located on the rear panel of the RIO Drop Modules and are
used for setting RIO drop addresses (refer to the following illustration and table).
SW1 (top switch) sets the upper digit (tens); SW2 (bottom switch) sets the lower digit
(ones). The illustration below shows the correct setting for an example address of
11.
The following table shows the node addresses of the SW1 and SW2 switches.
SW1 and SW2 Address Settings
Node Address SW1 SW2
1 ... 9 0 1 ... 9
10 ... 19 1 0 ... 9
20 ... 29 2 0 ... 9
30 ... 39 3 0 ... 9
40 ... 49 4 0 ... 9
50 ... 59 5 0 ... 9
60 ... 64 6 0 ... 4
Note: If "0" or an address greater than 32 is selected, the module displays a
flashing ERROR A and ERROR B LED indicating an error condition. Only
addresses 2 - 32 are valid.
1
3
0
9
2
6
4
5
8
7
1
3
0
9
2
6
4
5
8
7
SW1 (Tens)
SW2 (Ones)
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
Vue de la page 278
1 2 ... 274 275 276 277 278 279 280 281 282 283 284 ... 899 900

Commentaires sur ces manuels

Pas de commentaire