Schneider Automation Modicon Quantum Ethernet Guide de l'utilisateur Page 703

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 900
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 702
I/O Modules
35013379 02 October 2007 703
Zoom Screen
Selection
Descriptions
Output Shutdown State - Determines the module output states if backplane
communication is lost (i.e., no "Active" LED on module).
Fail States - Module output state choices if selected in "Output Shutdown State"
menu.
Output Shutdown State:
Fail States
Disabled
Disabled: Forces all outputs to be in the OFF state.
Fail States: Group outputs are per the selection made in the “Fail States” column.
Fail States
Outputs OFF
Last Value
User Defined
Outputs OFF: Group outputs turn OFF
Last Value: Group outputs remain in the state they were in.
User Defined: Group output states may be individually selected in the
“User Defined Values” column to be ON or OFF.
Choices If Selected:
00000000
Lowest Numbered
Group Output (Ch 1, 9, 17, 25)
Highest Numbered
Group Output (Ch 8, 16, 24, 32)
0 = OFF
1 = ON
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com
Vue de la page 702
1 2 ... 698 699 700 701 702 703 704 705 706 707 708 ... 899 900

Commentaires sur ces manuels

Pas de commentaire