Intelligent/Special Purpose
400
35013379 02 October 2007
The following table shows the operational specifications for high speed input.
The following table shows the operational specifications for discrete inputs.
The following table shows the operational specifications for discrete outputs.
The following table shows the operational specifications for analog input.
High Speed Input
Position Capture Time 250 μs max
Isolation 500 V to system bus
Pulse Width 25 μs
Minimum Time Between
Successive Captures
20 ms
Discrete Inputs
Number 7
Scan Time 1.5 ms
Isolation 500 V to system bus
Discrete Outputs
Number 3
Update Time 10 ms max
Isolation 500 V to system bus
Reset State 0 V, nominal
On State 24 V, nominal
Output Type Totem pole (sink/source)
Protection Short circuit, overvoltage
Fault Overcurrent detected
Analog Input
Number 1
Scan Time 15 ms
Data User configurable
Range +/- 10 V
Accuracy +/- 100 mV,
plus offset