I/O Modules
35013379 02 October 2007 691
Fuse Locations The following figure shows the fuse locations for the DDO88500 module.
Note: Each output point is protected by an over current sense circuit. When an
over current condition is detected, the point is turned OFF, its LED fault indicator is
turned ON, and the appropriate bit is set in the module fault register.
The output point will be turned OFF after a short is detected. A fault greater than
9.4 A will guarantee that the point will be turned OFF and will latch the output point
in the OFF state. To clear a fault, the point must be commanded OFF in user logic.
Possible danger to equipment or personnel.
Turn off power to the module and remove the field wiring terminal strip to gain
access to fuses.
Failure to follow these instructions can result in injury or equipment damage.
CAUTION
Note: At a minimum, Modsoft V2.40, ProWorX NxT V2.0, or Concept V2.0, is
required to configure this module.
140
DDO 885 00
vdc out
X
Fuse Locations
Points
1-6
Points
7-12