Schneider Automation Modicon Quantum Ethernet Guide de l'utilisateur Page 669

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 900
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 668
I/O Modules
35013379 02 October 2007 669
Group to Group 500 Vac rms for 1 minute
Output to Bus 1780 Vac rms for 1 minute
Fault Detection Blown fuse detect, loss of field power
Bus Current Required 330 mA
Power Dissipation 1.75 W + 0.4 V x Total Module Load Current
External Power 19.2 ... 30 Vdc
Fusing
Internal 5A fuse for each group. Modicon Part # 043502405. For
the location of the fuses see Fuse Locations, p. 670.
External Each group is protected with a 5A fuse to protect the
module from catastrophic failure. The group fuse is not
guaranteed to protect each output switch for all possible
overload conditions. It is recommended that each point
be protected with a 3/4 A, 250 V fuse,
(Part # 57-0078-000).
Specifications
Possible danger to equipment or personnel.
Turn off power to the module and remove the field wiring terminal strip to gain
access to fuses.
Failure to follow these instructions can result in injury or equipment damage.
CAUTION
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com